XNUMX. The motor can't rotate after power on, but there is no abnormal noise, no strange smell and smoke
1. The cause of the failure:
The power is not connected (at least two phases are not connected)
Fuse blown (at least two phase blown)
The overcurrent relay is adjusted too small
Control device wiring error
2. Troubleshooting
Check whether there are breakpoints at the power circuit switch, fuse, and junction box, and repair it.
Check the fuse type, the cause of the fuse, and replace it with a new fuse
Adjust the setting value of the relay to cooperate with the motor
Correct the wiring
XNUMX. The motor does not rotate after power-on, and then the fuse is blown
1. The cause of the failure
One-phase power supply is missing, or the fixed and dry coil is connected oppositely
Short circuit between stator windings
Stator winding is grounded
Stator winding wiring error
Fuse section is too small
The power cord is shorted or grounded
2. Troubleshooting
Check whether one phase of the knife switch is not closed, or one phase of the power circuit is disconnected, and eliminate the reverse connection fault
Detect the short-circuit point and repair it
Eliminate grounding
Detect misconnections and correct them
Replace the fuse
Eliminate ground points
XNUMX. The motor does not rotate after power-on, and there is a buzzing sound
1. The cause of the failure:
There is an open circuit in the stator and rotor windings (one-phase disconnection) or one-phase power loss
The lead wire of the winding is disconnected from the beginning and the end is wrong or the winding is connected reverse
The power circuit contacts are loose and the contact resistance is large
The motor load is too large or the rotor is stuck
Power supply is low
The small motor assembly is too tight or the grease in the bearing is too hard
Bearing stuck
2. Troubleshooting
Find the breakpoint and fix it
Check the polarity of the winding; determine whether the end of the winding is correct
Tighten the loose wiring screws, use a multimeter to judge whether each connector is falsely connected, and repair it
Reduce load or detect and eliminate mechanical failures
Check whether the connection method is wrong, whether the voltage drop is too large due to the power wire is too thin, and correct it
Reassemble to make it flexible and replace qualified grease
Repair the bearing